WFI LOOP SYSTEM
o Material of construction - SS 316L.
o Internals electro polished to Ra < 0.8.
o Externals Mechanically polished to 180 grit finish.
o Welding technique - Automatic Orbital Welding.
o All interconnections through triclovers.
o All valves are of self draining type.
o All gaskets are of Teflon.
o Dead leg not more than 6d for d < 30mm.
o Dead leg not more than 3d for d >/=30mm.
o Entire installation will be completely drainable.
o Slope of the low point must be 1: 100 minimum
Ascessories supplied with the WFI LOOP SYSTEM
o WFI circulation pump.
o Saunders diaphragm valves.
o Temperature Indicator cum Controller.
o Flow Indicator cum Totalizer.
o Conductivity Indicator cum Controller.
o Sanitary Diverting Valve.
o Back Pressure Valve.
o Panel board with Data Logger, printer and alarm system. |
|